Series 24


Products > Commercial Boilers > Series 24

Picture of the Series 24


The Series 24 is a cast-iron water or steam boiler designed for use with light oil, gas, or a light oil-gas combination. The Series 24 is designed for installation with either a standard chimney or a pressurized vent system. The boiler has a swing-open front door for easy service and inspection.

The Series 24 is available in 10 sizes, with heating capacities ranging from 342,000 to 1,852,000 BTU/hr.

This boiler is easily assembled with draw rods, and all the maintenance access areas are located on the left side, simplifying servicing.


Print Product Brief
Print Product Brochure

Air Conditioning Heating and Refrigeration Institute AHRI MemberConstructed and tested in accordance with ASME American Society of Mechanical Engineers Section FourAir Conditioning Heating and Refigeration Institute AHRI Certified Logo
Type: Commercial
Heat Exchanger: Cast Iron
Fuel: Oil, Gas (Natural or LP)
Input: Oil: 3.05 - 16.00 GPH
Gas: 438 - 2320 MBH
Combustion Efficiency: Oil: 84.7% - 86.0%
Gas: 82.1% - 82.5%
Venting: Chimney or Forced Draft
Ignition: N/A
Trim: Water or Steam
Domestic Water: Optional - Tankless Coil
Burner: Beckett
Configuration: Knocked Down

BOILER MODEL HORSE-POWER GROSS OUTPUT
(MBH)
NET I=B=R RATING BURNER
INPUT
HEATING SURFACE
(SQ. FT.)
NET
FIREBOX
VOLUME
(CU. FT.)
PRESSURE
IN
FIREBOX
("W.C.")
WATER CONTENT
(GAL.)
BOILER WEIGHT
w/ WATER
(LBS.)
SQ. FT.
STEAM
MBH
STEAM
MBH
WATER
OIL
(GPH)
GAS
(MBH)
STEAM WATER STEAM WATER STEAM WATER
                               
24-03 10.2 342 1071 257 297 3.05 438 34.2 37.0 3.2 0.33 44.5 66 1439 1618
24-04 14.1 471 1471 353 410 4.10 594 48.6 54.3 4.8 0.38 53.0 75 1811 1995
24-05 18.9 634 1983 476 551 5.50 792 63.0 71.5 6.4 0.31 61.5 84 2184 2372
24-06 23.8 797 2492 598 693 6.90 990 77.5 88.8 7.9 0.38 70.0 93 2557 2749
24-07 28.0 937 2929 703 815 8.10 1174 91.9 106.0 9.5 0.36 78.5 102 2930 3126
24-08 32.5 1087 3396 815 945 9.40 1358 106.3 123.3 11.0 0.35 87.0 111 3303 3503
24-09 39.3 1316 4146 995 1148 11.40 1641 120.7 140.5 12.6 0.35 95.5 120 3676 3880
24-10 45.0 1505 4788 1149 1309 13.00 1867 135.1 157.8 14.2 0.40 104.0 129 4048 4257
24-11 50.5 1690 5429 1303 1470 14.60 2093 149.5 175.0 15.7 0.45 112.5 138 4421 4634
24-12 55.3 1852 5983 1436 1610 16.00 2320 164.0 192.3 17.3 0.49 121.0 147 4794 5011
                               
  Notes:
  1. Ratings shown above apply at altitudes up to 1,000 feet on oil and 2,000 feet on gas. For altitudes above those indicated, the ratings should be reduced at the rate of 4% for each 1,000 feet above sea level.
  2. Fire box volume does not include added volume of 8" extended burner mounting plate (BMP). If 8" is specified,  add 0.7 cu. ft. to volume listed above.
  3. Boiler ratings are based on 12.5% CO2 (oil) and 9.7% CO2 (natural gas), + .10" (inches) water column pressure at boiler flue outlet.
  4. Consult manufacturer for installations having unusual piping and pick-up requirements, such as intermittent system operation, extensive piping systems, etc.
  5. The I=B=R  burner capacity in GPH is based on oil having a heat value of 140,000 BTU per gallon.
  6. I=B=R net ratings shown are based on piping and pick-up allowances which vary from 1.333 to 1.289 for steam and 1.15 for water.
  7. Maximum Allowable Working Pressure: Steam Boiler - 15 PSI, Water Boiler - 50 PSI
  8. Standard Safety (Relief) Valve Set Pressure: Steam Boiler - 15 PSI, Water Boiler - 30 PSI   

BOILER MODEL SECTIONS 'A' 'B' # OF STEAM RISERS 'C' 'D' MAX # OF
HEATERS
'E'
FLUE OUTLET
DIAMETER
'F'
BURNER MOUNTING
PLATE WIDTH
'G'
BECKETT1 APPROX.
K.D. BLR.
SHIPPING
WEIGHT
(LBS)
CF OIL
'H'
CG GAS
'H'
                         
24-03 3 18-1/4 12 1 --- 9-1/8 1 7 8 9-3/4 20-7/8 1363
24-04 4 24-1/4 18 1 --- 12-1/8 1 7 8 11-3/4 21-5/8 1675
24-05 5 30-1/4 24 1 --- 15-1/8 1 8 8 11-3/4 21-5/8 1987
24-06 6 36-1/4 30 1 --- 18-1/8 2 8 4 20-5/8 21-5/8 2273
24-07 7 42-1/4 36 2 --- 21-1/8 2 8 4 20-5/8 28-5/8 2589
24-08 8 48-1/4 42 2 --- 24-1/8 2 10 4 20-5/8 28-5/8 2901
24-09 9 54-1/4 48 2 --- 27-1/8 3 10 4 21-1/8 29-1/8 3282
24-10 10 60-1/4 54 2 --- 30-1/8 3 10 4 21-1/8 29-1/8 3614
24-11 11 66-1/4 60 2 --- 33-1/8 3 12 4 22-5/8 29-1/8 3925
24-12 12 72-1/4 66 3 30 36-1/8 4 12 4 22-5/8 29-1/2 4252

Series 24 Top dimensions
Click for larger view of the Series 24
(Click for larger image)


Series 24 Literature

Date: 2/24/2011 2:13:11 PM
Size: 2.3 mb


Series 24 Installation Manual

Date: 7/29/2011 11:22:48 AM
Size: 6.5 mb


Series 24 Target Wall Installation

Date: 11/29/2010 2:43:49 PM
Size: 232.34 kb