General Configuration of the Base Model

 

 

COMMERCIAL - SERIES 16 SPECIFICATIONS

Boiler
Model
No.
No. of
Sections
Natural or LP Gas Dimensions Water
Content
(Gallons)
Shipping
Weight
(Lbs)
Input
(BTUH)
D.O.E
heating
Capacity
(BTUH)
IBR
Net
Rating
Water
(BTUH)
AFUE
(%)
A B C D E F
16-325 6 325,000 260,000 226,000 80.0 23-3/4 11-7/8 8 27-13/16 18 60-5/16 13.9 770
16-390 7 390,000 312,000 271,000 80.0 27-1/2 13-3/4 9 28-13/16 18 61-5/16 15.9 875
16-455 8 455,000 364,000 317,000 80.0 31-1/4 15-5/8 9 30-13/16 20 63-5/16 17.9 980
16-520 9 520,000 416,000 362,000 80.0 35 17-1/2 10 33-1/2 22 66 19.9 1080
16-585 10 585,000 468,000 407,000 80.0 38-3/4 19-3/8 10 33-1/2 22 66 21.9 1200
  1. Ratings shown are for installations at sea level and elevations up to 2,000 feet. For elevations above 2,000 feet, ratings should be reduced at the rate of 4% for each 1,000 feet above sea level.

  2. When ordering, use suffix EN for natural gas with electronic ignition and EL for LP gas with electronic ignition.

  3. Net I=B=R ratings shown are based on normal I=B=R piping and allowance of 1.15. Consult the man manufacturer for installations having unusual piping and pickup requirements such as intermittent system of operation, extensive piping systems, etc.

  4. Maximum allowable working pressure is 50 PSI.

 

Optional Equipment
  • Base for installation on combustible floors
  • CSD-1 Control System
  • 50 PSI safety relief valve
  • Vent damper
Important:
  1. Not for direct installation on combustible flooring. A heat shield is required and available for installation on combustible floors and on concrete floors which are over a material that is subject to melting (PVC,PEX Radiant Tubing, etc.). Not for installation on carpet even with a heat shield
  2. External draft hood supplied-may not be cut or altered.