COMMERCIAL - SERIES 32 SPECIFICATIONS
Steam Boiler Piping, Four, Five, or Six Supply Connections, Gravity Return

Minimum Pipe Sizes

1615* 1710* 1805* 1900* 1995* 2090* 2185** 2280** 2375** 2470** 2565** 2660*** 2755*** 2850***
3" 3" 3" 3" 3" 3" 3" 3" 3" 3" 3" 3" 3" 3" A
4" 4" 4" 4" 4" 4" 4" 4" 4" 4" 4" 4" 4" 4" B
6" 6" 6" 6" 6" 6" 6" 6" 6" 6" 6" 6" 6" 6" C
- - - - - - 8" 8" 8" 8" 8" 8" 8" 8" D
- - - - - - - - - - - - 8" 8" E
6" 6" 6" 6" 6" 6" 8" 8" 8" 8" 8" 8" 8" 8" F
2-1/2" 2-1/2" 3" 3" 3" 3" 3" 3" 3" 3" 4" 4" 4" 4" G
2" 2" 2-1/2" 2-1/2" 2-1/2" 2-1/2" 2-1/2" 2-1/2" 2-1/2" 2-1/2" 3" 3" 3" 3" H


NOTE: FOR BOILER MODELS 1615 THROUGH 2850 IT IS PERMISSIBLE
TO FABRICATE THE ENTIRE LENGTH OF THE STEAM HEADER USING
THE LARGEST PIPE DIAMETER AS INDICATED IN C, D, OR E FOR A GIVEN SIZE BOILER IN THIS RANGE.
*FOUR SUPPLY RISERS REQUIRED   **FIVE SUPPLY RISERS REQUIRED   ***SIX SUPPLY RISERS REQUIRED