RATINGS SPECIFICATIONS
Boiler
Model |
I=B=R
Gross Input |
I=B=R
Gross Output |
I=B=R
Net Rating Water MBH |
Approx.
Dry Weight Lbs. |
Vent
Connect. Dia. Inches |
I=B=R
Vent Dia. Inches |
Dim.
Inches |
Water
Content Gal. |
Draft
Loss Inc. W.C. |
| Oil
GPH |
Gas
MBH |
MBH |
BHP |
| FW-4 |
3.0 |
433 |
355 |
10.6 |
309 |
948 |
8 |
7 |
32 |
15.8 |
.16 |
| FW-5 |
4.0 |
577 |
478 |
14.2 |
416 |
1124 |
8 |
7 |
37 |
19.0 |
.27 |
| FW-6 |
5.0 |
722 |
600 |
17.9 |
522 |
1301 |
10 |
8 |
42 |
22.2 |
.39 |
| FW-7 |
6.0 |
866 |
723 |
21.6 |
629 |
1477 |
10 |
9 |
47 |
25.4 |
.51 |
| FW-8 |
7.5 |
1082 |
907 |
27.1 |
789 |
1654 |
10 |
10 |
52 |
28.5 |
.62 |
| FW-9 |
9.0 |
1299 |
1091 |
32.6 |
949 |
1831 |
10 |
10 |
57 |
31.7 |
.75 |
BURNER
DATA OPTIONS
| Boiler
Model |
Burner
Motor |
Burner
Model Light Oil |
Burner
Model Gas |
Burner
Model Gas/Oil Comb. |
Gas
Train Size |
Min.
Gas Press. Req. @ Burner in W.C. |
| MFG. |
HP |
Voltage |
| FW-4 |
Beckett |
1/3 |
120-1 |
CF-500 |
- |
- |
- |
- |
| Power
Flame |
1/3 |
120-1 |
C1-0 |
C1-G-10 |
C1-GO-10 |
1-1/4 |
5.5 |
| FW-5 |
Beckett |
1/3 |
120-1 |
CF-800 |
- |
- |
- |
- |
| Power
Flame |
1/3 |
120-1 |
C1-0 |
C1-G-10 |
C1-GO-10 |
1-1/4 |
5.5 |
| FW-6 |
Beckett |
1/3 |
120-1 |
CF-800 |
- |
- |
- |
- |
| Power
Flame |
1/3 |
120-1 |
C1-0 |
C1-G-10 |
C1-GO-10 |
1-1/4 |
5.5 |
| FW-7 |
Beckett |
1/3 |
120-1 |
CF-1400 |
- |
- |
- |
- |
| Power
Flame |
1/3 |
120-1 |
C1-0 |
C-G-10 |
C1-GO-10 |
1-1/4 |
5.5 |
| FW-8 |
Beckett |
1/2 |
120-1 |
CF-1400 |
- |
- |
- |
- |
| Power
Flame |
3/4 |
230-1 |
C2-OA |
C2-G-15 |
C2-GO-15 |
1-1/2 |
7.0 |
| FW-9 |
Beckett |
1/2 |
120-1 |
CF-2300 |
- |
- |
- |
- |
| Power
Flame |
3/4 |
230-1 |
C2-OA |
C2-G-15 |
C2-GO-15 |
1-1/2 |
7.0 |
Click
Here For Print Version
|
 |
 |