COMMERICAL - FW MODEL SPECIFICATIONS
RATINGS
SPECIFICATIONS
| Boiler Model | I=B=R Gross Input |
I=B=R Gross Output |
I=B=R Net Rating Water MBH |
Approx. Dry Weight Lbs. | Vent Connect. Dia. Inches | I=B=R Vent Dia. Inches |
Dim. Inches | Water Content Gal. | Draft Loss Inc. W.C. | ||
| Oil GPH | Gas MBH | MBH | BHP | ||||||||
| FW-4 | 3.0 | 433 | 355 | 10.6 | 309 | 948 | 8 | 7 | 32 | 15.8 | .16 |
| FW-5 | 4.0 | 577 | 478 | 14.2 | 416 | 1124 | 8 | 7 | 37 | 19.0 | .27 |
| FW-6 | 5.0 | 722 | 600 | 17.9 | 522 | 1301 | 10 | 8 | 42 | 22.2 | .39 |
| FW-7 | 6.0 | 866 | 723 | 21.6 | 629 | 1477 | 10 | 9 | 47 | 25.4 | .51 |
| FW-8 | 7.5 | 1082 | 907 | 27.1 | 789 | 1654 | 10 | 10 | 52 | 28.5 | .62 |
| FW-9 | 9.0 | 1299 | 1091 | 32.6 | 949 | 1831 | 10 | 10 | 57 | 31.7 | .75 |
| Boiler Model | Burner Motor | Burner Model Light Oil | Burner Model Gas | Burner Model Gas/Oil Comb. | Gas Train Size | Min. Gas Press. Req. @ Burner in W.C. | ||
| MFG. | HP | Voltage | ||||||
| FW-4 | Beckett | 1/3 | 120-1 | CF-500 | - | - | - | - |
| Power Flame | 1/3 | 120-1 | C1-0 | C1-G-10 | C1-GO-10 | 1-1/4 | 5.5 | |
| FW-5 | Beckett | 1/3 | 120-1 | CF-800 | - | - | - | - |
| Power Flame | 1/3 | 120-1 | C1-0 | C1-G-10 | C1-GO-10 | 1-1/4 | 5.5 | |
| FW-6 | Beckett | 1/3 | 120-1 | CF-800 | - | - | - | - |
| Power Flame | 1/3 | 120-1 | C1-0 | C1-G-10 | C1-GO-10 | 1-1/4 | 5.5 | |
| FW-7 | Beckett | 1/3 | 120-1 | CF-1400 | - | - | - | - |
| Power Flame | 1/3 | 120-1 | C1-0 | C-G-10 | C1-GO-10 | 1-1/4 | 5.5 | |
| FW-8 | Beckett | 1/2 | 120-1 | CF-1400 | - | - | - | - |
| Power Flame | 3/4 | 230-1 | C2-OA | C2-G-15 | C2-GO-15 | 1-1/2 | 7.0 | |
| FW-9 | Beckett | 1/2 | 120-1 | CF-2300 | - | - | - | - |
| Power Flame | 3/4 | 230-1 | C2-OA | C2-G-15 | C2-GO-15 | 1-1/2 | 7.0 | |