MAXI-THERM 2 SPECIFICATIONS

Performance Specifications
Hydronics Institute Tested
Performance ratings
Model
MT040GBR MT050GBR MT080GBR MT120GBC
First Hour Rating (Gal/hr) 187.5 192.5 221.0 407.5
Cont. Draw Rating (Gal/hr) 162.0 160.0 162.8 327.9
Standby Heat Loss (F/hr) 1.0 0.9 0.8 0.7
Min. Boiler Output (BTU/hr) 105,966 104,048 106,496 214,513
Boiler Water Flow (Gal/min) 8.0 8.0 8.0 10.6
Coil Head Loss (ft w.c.) 0.60 0.60 0.60 1.80
Notes:
  1. Ratings based upon the following conditions: 180F boiler supply, 58F cold water in, 135F domestic water out.
  2. The ratings shown were obtained at the heat source output rates and heat source follow rates shown in the chart above. Other results will be obtained under  different conditions.
  3. I=B=R certification applies only to the ratings in the chart above.
Other Specifications
 
  Model
MT040GBR MT050GBR MT080GBR MT120GBC
Coil Surface (sq ft.) 14.2 14.2 14.2 27.2
Tank Volume (Gal) 36.5 45.4 67.1 100.7
Net Weight (lbs) 208 226 230 445
Filled Weight (lbs) 512 604 786 1285

Dimensions (inches)

Model A B C D E F
MT040GBR 24 36 29-3/4 36-3/4 5-3/8 27-1/2
MT050GBR 26 36 29-3/4 36-3/4 5-3/8 27-1/2
MT080GBR 24 59 52-7/8 59-3/4 5-3/8 28-1/2
MT120GBC 28-1/4 62-1/2 55-3/4 63-1/4 6-3/8 48-3/4